In normal UPS use, FGET use maintenance-free VRLA battery, whose design life is typically either five or ten years, with some fifteen-year sizes available.
Battery Use and Maintenance:
6) Please keep it at low temperature. Please change it while there is liquid leaking or damage.
Battery Out Size:
Capacity |
20 hour rate(0.85A ) |
17AH |
10 hour rate(1.615A ) |
16.15AH |
|
5 hour rate(2.72A ) |
13.6AH |
|
Internal Resistance |
Full charged Battery at 25 'C(77'F ) |
≤25mΩ |
Capacity affected by Temp |
40'C (104F) |
102% |
25'C (77'F) |
100% |
|
0'C (32'F) |
85% |
|
(-15'C )5'F |
65% |
|
Self-Discharge |
Capacity after 3 month storage |
90% |
Capacity after 6 month storage |
80% |
|
Capacity after 12 month storage |
62% |
|
Charge |
Initial Charging Current less than 26 A |
|
Voltage 14.4-15.0V |
||
Voltage 13.5-13.8V |
Our Services:
Samples and OEM, Warranty and After-Sale Service:
Sample can be provided for quality testing
Product Series | AS series small size(Capacity below 33Ah) | AM series mediuml size(6V,12V,Capacity 33Ah to 65Ah) | SL series large size(2V, Capacity above 65Ah) |
Main Applications | 1) Small UPS 2) Baby carriage, scooter, lawn mower, bag car 3) Electronic scales, portable lamps, table lamps, garden lamps, electric fans 4) Instrumentation equipment such as electronics, power tools, and electric toys, etc. 5) Car starter, generator 6) Solar/ wind energy indicator lights, signal lights, emergency lights, fire alarms and security systems 7) Consumer products supporting power supply, etc. |
1) Medium and large UPS 2) Banking, finance, traffic signals (metro, railway, highway, air station, navigation mark, etc.) system 3) Power DC screen 4) Emergency power supply (EPS) 5) DC power supply for hospitals, laboratories, schools, and research institutes 6) Electronics, equipment 7) Automation control system, etc. |
1) Communication base station/office 2) Backup power supply for power DC screen, power communication backup power supply 3) Large IDC machine room backup power supply, large UPS backup power supply 4) Solar/ wind energy off-grid energy storage system |
General Features | ●Affordable, consumer design ●Children's car, lamps, scales, etc. adopt cycle technology, deep cycle and long discharge life ●The starter adopts cast welding and wall welding technology, and has excellent super-current discharge performance. |
●High capacity design, longer standby time ●High corrosion-resistant multi-alloy grid, long life of float charge ● A variety of sizes, suitable for a variety of equipment or cabinet installation |
●Thick plate, low density, internalized design, long life of floating charge, suitable for standby power supply |
Battery Use and Maintenance:
1) Please use constant-voltage charge.
2) In floating charge, the voltage is 2.23 to 2.27 per unit cell.
3) In cycle use, the voltage is 2.35 to 2.45 per unit cell, the max. Current is no more than 25%° C
4) Please do tighten the bolts to avoid sparkle and poor contact when the battery is in use.
5) Please do not use it near the heat source and open flame.
6) Please keep it at low temperature. Please change it while there is liquid leaking or damage.
Carton Packing
20, 10 or 4 pieces in one carton for batteries smaller than 12V24AH,one in one carton for larger batteries.
Batteries Layer
Load Lead acid batteries 3-5 layers high with cardboard between each layer, and stretch wrap. Make sure to catch the top of the pallet to help anchor it.
Fumigation Free Tray
As Lead Acid batteries are very heavy, we all use fumigation free tray to transport them.
FGET, it is highly resistant to battery acid, oxidation and heat, and can maintain its shape and strength after prolonged exposure to sever environmental conditions. Customized specifications are available.
Battery Charging
In the fully charged state, the negative plate consists of lead, and the positive plate lead dioxide, with the electrolyte of concentrated sulfuric acid.
Produce line